GDPD-414 Mea ʻImi Hoʻokuʻu ʻĀpana Hiki



Nui
ʻāpana
UHF sensor,
ʻano poepoe,kūpono no GIS
UHF sensor, rectangle type, kupono no ka mana uwea, transformer, switchgear



HFCT, kūpono no ka uwea mana, transformer
ʻO ka mea ʻike TEV,
kūpono no ka mea hoʻololi
ʻO ka mea kani kani kani, kūpono no nā mea hoʻololi, nā mea hoʻololi

ʻO nā kiʻi ma luna aʻe no ka ʻike mua.
Hoʻohana ka GDPD-414 Portable (GDPD-414H handheld) Partal Discharge Detector i ka ʻōnaehana hoʻāʻo naʻauao wikiwiki (Soft No. 1010215, helu inoa inoa inoa 14684781 (14684481)).Hiki iā ia ke hoʻonohonoho maʻalahi i nā sensor like ʻole e like me nā huahana like ʻole e hoʻāʻo ʻia.ʻO TEV, kani ultrasonic a me HFCT he kūpono no ka ʻike ʻana i ka hoʻokuʻu ʻana i ka ʻāpana kiʻekiʻe-voltage switchgear a me ke apo network cabinet;He kūpono ka Ultrasonic a me ka UHF no ka ʻike ʻana i ka GIS;He kūpono ka Ultrasonic a me ka HFCT no ka hoʻāʻo ʻana i ke kaula mana.Hiki i ka ʻōnaehana hōʻoia akamai i kūkulu ʻia ke kālailai i ka ʻikepili hoʻāʻo a hoʻoholo i ka ikehu hoʻokuʻu a me nā ʻāpana hiki.Hoʻohana nui ia i ka mana uila a me ke kaʻaahi.

Kani ultrasonic a me TEV mea ike (2-i-1)
●E hoʻopaʻa i ka papa hōʻailona DSP/FPGA kiʻekiʻe, 4-channel synchronous data acquisition.
●Pūnaehana lako polokalamu: polokalamu loiloi ma muli o ka ʻōnaehana hoʻokomo ʻia ʻo ARM
●Hiki ke hoʻonohonoho ʻia nā kaha 6/8/16
●8.1 iniha papa a i ʻole Thinkpad notebook ma ke ʻano he koho
●Hiki ke hoʻonohonoho ʻia nā kaha 6/8/16 e like me nā koi like ʻole o ka mea kūʻai aku.
●Hiki ke hōʻike i nā palapala 'āina PRPS a me PRPD, nā kiʻi ellipse, nā palapala 'āina hoʻokuʻu, nā palapala 'āina QT, nā palapala 'āina NT, nā palapala 'āina kumulative PRPD, nā palapala 'āina fai-QN o kēlā me kēia kahawai hōʻailona.
● Hōʻike nā ʻano hōʻailona ʻekolu kala o ka ʻulaʻula, melemele a me ka uliuli i ke koʻikoʻi o ka hoʻokuʻu hapa.
Hiki i ka mea kūʻai ke koho i nā sensor e like me nā mea i hoʻāʻo ʻia:
Nā mea ʻike | TEV/AE/HFCT | AE/UHF | AE/HFCT |
Nā mea i hoʻāʻo ʻia | HV Swichgear a me Ring keena waihona |
GIS |
Uea |
PD hōʻailona loaʻa host | |
CPU hana pinepine | 1.2GHz / 800MHz |
ʻōnaehana hana | Linx i hoʻokomo ʻia i ka ʻōnaehana hana |
awa pūnaewele uwea | awa pūnaewele LAN |
awa pūnaewele uwea ole | ʻO WiFi uea i kūkulu ʻia i loko (koho) |
Pūnaehana holo hoʻomanaʻo | 1G / 512M |
Pūnaehana waihona hoʻomanaʻo | 512M / 256M |
ʻIke pinepine ʻikepili | 250MHz / 80MHz |
Kaila ʻike kani ultrasonic | |
Laulā ana | 0-60mV |
Laulā ʻike alapine | 20~200kHz |
Kaila ʻike UHF | |
ʻIke pinepine | 300~1800MHz / 300~1500MHz |
Laulā ana | -80~10dBm |
Kuhihewa | ±1dBm |
Olelo Hooholo | 1dBm |
Kaila ʻike HFCT | |
Laulā pinepine | 0.5~100MHz |
Kuhihewa | ±1dB |
Laina Paʻi | 60dB |
Laulā ana | 0-100mV |
Ka pololei | 1dB |
Kaila ʻike TEV | |
Laulā pinepine | 3~100MHz |
Kuhihewa | ±1dB/mV |
ʻO ka ʻike | 0.01mV |
Laulā ana | 0-60dB/mV |
Olelo Hooholo | 1dBm/mV |
Batri | |
Pākaukau i kūkulu ʻia | Baila Lithium, 12V, 4400mAh / Lithium Battery, 12V, 2000mAh |
E hoʻohana i ka manawa | ma kahi o 8 hola / ma kahi o 6 hola |
Ka manawa hoʻouka | Ma kahi o 2 hola |
Paʻa pākaukau | ʻO ka pale ʻana i ka overvoltage a me ka over-current |
Ka hoʻouka ʻana i ka pākaukau | |
Volta koho | 12.6V |
Ka hoʻouka ʻana i kēia manawa | 2A |
Hana wela | -20 ℃-60 ℃ |
ʻO ka haʻahaʻa hana | <80% |
GDPD-414H pahu hōʻike paʻa lima (papa ʻoihana) | |
CPU | Intel Quad Core Atom Z3735F |
GPU | Intel HD Graphic (Gen7) |
Flash | 32GB |
RAM | 2GB |
ʻōnaehana hana | Windows10 |
Hōʻike | 8.1 iniha 1280×800 IPS pale |
Hoʻopili pūnaewele | Wifi a me Bluetooth |
Batri | 3.7V 8500mAH polymer lithium ion pākahi |
ʻO Thinkpad Laptop a i ʻole PC Papa | |
Nui | |
Ka nui o ka hihia mea kōkua / ka nui o ka hoʻokipa PD | 395mm*295mm*105mm / 240mm*165mm*55mm |
Kaumaha hoʻokipa PD | 3kg / 0.65kg |
Ka nui pahu pahu PD / Hōʻike i ka nui o ka pahu pahu | 570mm*360mm*240mm / 395mm*295mm*105mm |
Hōʻike i ke kaumaha o ka pahu papa | 0.85 kg |
Nui pahu holoʻokoʻa | 570mm * 360mm * 240mm |
Kaiapuni hana | |
Hana wela | -20 ℃~50 ℃ |
Ka haʻahaʻa kaiapuni | 0~90%RH |
pae IP | 54 |
GDPD-414H Hoʻokuʻu hapa ʻAha Paʻa