ʻO ka pololei o nā hopena hoʻāʻo a me ka pololei o nā hoʻoholo hoʻoholo e pili ana i ka ʻelele o nā laʻana i lawe ʻia.ʻAʻole wale ke kumu o ka hoʻoheheʻe ʻana i ka mana kanaka, nā kumu waiwai a me ka manawa, akā ke alakaʻi nei i nā hopena hewa a me nā poho nui aʻe.No ka aila laʻana me nā koi kūikawā no ka laʻana, e like me ke kinoea spectrometry kālailai i loko o ka aila, micro wai i ka aila, furfural i ka aila, metala kālailai i loko o ka aila a me ka pollution particle (a maemae) o ka aila, etc. ka ipu laʻana a me ke ʻano a me ka manawa o ka mālama ʻana.
I kēia manawa, ua helu ʻia nā ʻōkuhi laʻana no ka mea hoʻoponopono chromatographic:
HV Hipot GDC-9560B Power System Oil Chromatography Analyzer
(1) No ka lawe ʻana i nā laʻana aila no ka loiloi chromatographic o ke kinoea i loko o ka aila, pono e hoʻohana ʻia kahi syringe lapaʻau maʻemaʻe a maloʻo 100mL me ka airtightness maikaʻi e lawe i nā laʻana ma kahi ʻano sila.ʻAʻole pono e loaʻa nā ea i loko o ka ʻaila ma hope o ka laʻana.
(2) Pono e hoʻokahe ʻia ka ʻaila i hōʻiliʻili ʻia ma ke kihi make o ke kahawai ma mua o ka laʻana, pono e hoʻokahe ʻia ʻo 2 ~ 3L ma mua o ka laʻana.Ke mānoanoa a lōʻihi ka paipu, pono e hoʻokuʻu ʻia ma ka liʻiliʻi ʻelua o kona leo.
(3) Pono e hoʻolaʻa ʻia ka paipu hoʻohui no ka laʻana, a ʻaʻole ʻae ʻia ka paipu wili i wili ʻia e ka acetylene ma ke ʻano he paipu hoʻohui no ka laʻana.
(4) Ma hope o ka laʻana, pono e hoʻomaʻemaʻe ʻia ke kumu o ka syringe e pale ai i ka hoʻopaʻa ʻana.
(5) Mai ka laʻana i ka nānā ʻana, pono e pale ʻia nā laʻana mai ka mālamalama a pono e hoʻouna ʻia i ka manawa e hōʻoia i hiki ke hoʻopau ʻia i loko o 4 mau lā.