ʻO GDJF-2008 mea hoʻoheheʻe hapa
Ke ana nei ka GDJF-2008 Partial Discharge Detector i ka hoʻokuʻu hapa no nā huahana e like me nā transformers, nā mea hoʻohui like, nā hoʻololi HV, nā mea hopu zinc monoxide a me nā kaula mana.Hiki iā ia ke hana i nā hoʻokolohua ʻano a nānā i ka hana insulation.
Loaʻa i kēia ʻano nā mea maikaʻi o ka naʻau kiʻekiʻe, ākea ākea o ka capacitance, i hoʻolako maikaʻi ʻia no ka ʻike ʻana i ka impedance unit a me nā ʻano ʻē aʻe o nā kaha alapine (9 i nā mea āpau).Ma hope o ka hoʻonohonoho kūpono, hiki ke heluhelu pololei ʻia ka nui o ka hoʻokuʻu ʻana.Hōʻike ʻia nā mita hōʻike a me nā kikohoʻe i ka manawa like.
Hoʻohana nui ʻia kēia mea ʻike i nā kikowaena mana, nā mea hana, a me nā ʻoihana.
●Ka wela wela: 0-40 ℃ ± 2 ℃.
●ʻAno haʻahaʻa: ≤80%
●Ka lako mana: 220V±10%, 50HZ.
●ʻAʻohe haʻalulu ikaika a me ka haʻalulu mechanical.
●Pono e hoʻokomo ʻia ka hāmeʻa i loko o ke kaiapuni me ka lepo ʻole a me ka corrosive, maikaʻi ventilation.ʻAʻole pono e hoʻopilikia ʻia e ka electromagnetic ikaika.
●Nā mea e pono ai ka honua: ke kū'ē honua <1Ω.
●E ho'āʻo ʻia ka laulā capacitance 6PF-250μF.
●Ke hoʻāʻo ʻana i ka naʻau (hōʻike ʻia ma ka Papa.1).
ʻāpana hoʻokomoʻAʻole. | ʻO ka mana hoʻopono | Unite | ʻIke (pC)(Kaapuni like ole) |
1 | 6-25-100 | pF | 0.02 |
2 | 25-100-400 | pF | 0.04 |
3 | 100-400-1500 | pF | 0.06 |
4 | 400-1500-6000 | pF | 0.1 |
5 | 1500-6000-25000 | pF | 0.2 |
6 | 0.006-0.025-0.1 | mF | 0.3 |
7 | 0.025-0.1-0.4 | mF | 0.5 |
8 | 0.1-0.4-1.5 | mF | 1 |
9 | 0.4-1.5-6.0 | mF | 1.5 |
10 | 1.5-6.0-25 | mF | 2.5 |
11 | 6.0-25-60 | mF | 5 |
12 | 25-60-250 | mF | 10 |
7R | Kūʻē |
| 0.5 |
●Pāʻani hoʻonui
Kūlana haʻahaʻa: 10KHZ, 20 KHZ, 40 KHZ (koho)
Kūlana kiʻekiʻe: 80 KHZ, 200 KHZ, 300 KHZ (koho)
● ʻO ka hoʻoponopono ʻana i ka amplifier
ʻO ka mana koʻikoʻi - aia he 6 mau mīkini no ka hoʻopaʻa ʻana, ʻo ka loaʻa o kēlā me kēia mīkini he 20±1db
Ka mana maikaʻi ≥ 20 db
● Nā puka makani manawa
Ka laula o ka pukaaniani, hiki ke hoololi ia 15o—150o
Kūlana pukaaniani, hiki ke hoʻololi ʻia 0o—170o
Hiki ke wehe ʻia nā puka makani ʻelua i ka manawa like a i ʻole kaʻawale.
● Meka hoʻokuʻu
Hōʻike kikohoʻe
Hōʻike PD: LED 3½ huahelu
0-100.0 palena o ka hewa <±3% (nui piha)
● Ke kumu manawa Ellipse
Ka pinepine: 50Hz a me ke alapine ʻole
He melemele ke kala hōʻike elliptic
Elliptic rotation: ʻo kēlā me kēia mīkini he 30 °, hiki ke hana i ka rotation 180 °.
Hōʻike: ellipse - laina pololei
Kiʻekiʻe alapine (frequency time base elliptical input voltage emi ma lalo o 220 V, mana komo <1 VA
● Laka nalu
Laka i ka nalu i makemake ʻia i kēlā me kēia manawa e maʻalahi i ka nānā ʻana a me ka nānā ʻana
● ʻO ka mika Voltage hoʻāʻo
Laulā: 100KV (Hiki ke hoʻonui ʻia)
Hōʻike 31/2 mīkini uila uila
Pono: ʻoi aku ka maikaʻi ma mua o ± 2% (nui piha)
● ʻO loko, ma waho o ka hana zero-mark
●Nui: 450×450×190 mm
●Kaumaha: ma kahi o 16kg