ʻO GDSF-311WPD 3-Ma-1 SF6 mea hoʻoponopono kinoea
He mea hana maikaʻi ʻo GDSF-311WPD (GDSF-411WPD) inā pono e hoʻāʻo i ka ʻike wai, ka maʻemaʻe a me nā huahana decomposition o ke kinoea SF6.ʻO ka mea koʻikoʻi o ka hoʻāʻo dew point ʻo DRYCAP® series sensor i hana ʻia e Finland Vaisala hui.Hoʻohana ʻia ka manaʻo infrared SF6 gas purity testing sensor i hana ʻia e European Sensor Company e hoʻāʻo i ka maʻemaʻe o ke kinoea SF6.Hoʻohana ʻia ka sensor electrochemical i hana ʻia e Mombabo Company ma Switzerland ma ke ʻano he sensing element no ka hoʻāʻo ʻana i nā huahana decomposition gas SF6.Me nā ʻāpana ʻenehana loea a me nā polokalamu algorithms maikaʻi loa o STMicroelectronics, ua hana mākou i kahi hanauna hou o 3-in-1 mīkini loiloi.
SF6Ka haʻahaʻa
●Ana 'ana: Resistive a Capacitive ana kumu
●Laulā ana: kahi hau -80 ℃--+ 20 ℃ (kākoʻo ppmv)
●Pono: ±1 ℃
(I ka wā ma lalo o 0 ℃ ka wela o ka hau, ʻo ka mea ʻike ke kumu hau)
●Manawa pane: 63% [90%]
+20→-20℃ Td 5s[45s]
-20→-60 ℃ Td 10s[240s]
●Hoʻoholo: 0.01 ℃
●Hiki ke hana hou: ± 0.5 ℃
●ʻĀpana hōʻike: ℃, ppm, ℃P20 (waiwai hoʻololi ʻia ma 20 ℃)
●Ka holo kinoea: 400-600ml / min
●Hōʻike kahe: 0-1000mL mika kahe kikohoʻe
●Pumi kinoea laʻana: ≤1MPa
SF6Maemae
●Ke ʻano ana: ʻO ke Kumu Anaʻe Infrared (Nir series sensors)
●Ana ana: 0 ~ 100% SF6
●Manawa pane: [90%] 60s
●Pono: ± 0.5%FS
●Hiki ke hana hou: ± 0.5%
●Hoʻoholo: 0.01%
●ʻĀpana hōʻike: %
SF6Nā Huahana Decomposition
●Ke ʻano ana ʻana: Kumukānāwai Ana Ana Electrochemical (Electrochemical series sensors)
●Laulā ana: H2S: 0 ~ 200ppmv
SO2: 0 ~ 200ppmv
CO: 0 ~ 500ppmv
HF: 0 ~ 50ppmv
●Pololei: H2S: 10ppmv ±3%
SO2: 10ppmv ±3%
CO: 50ppmv ±4%
HF: 10ppmv ±3%
●Hiki ke hana hou: H2S: 10ppmv ±2%
SO2: 10ppmv ±2%
CO: 50ppmv ±2%
HF: 10ppmv ±2%
●Hoʻoholo: 0.01ppmv
●ʻĀpana hōʻike: ppmv
●Ka lako mana: 220VAC±10%, 50Hz, AC/DC hoʻohana, over-charge protection, hoʻomau ka hana ʻaʻole i emi iho ma mua o 8hours.
●E hoʻohana i ka wela kaiapuni: -20--+60 ℃
●Ka haʻahaʻa kaiapuni: 90%RH
●Ka hopena o ka waiwai ana: ʻAʻohe hopena o ke kaomi a me ke kahe
●Ana: 395*295*155mm
●Kaumaha: ma kahi o 2kg.
GDSF-411WPD SF6Nā Huahana Decomposition
●Pono: H2S: <10ppmv ± 0.3ppmv;>10ppmv ±3%
SO2: <10ppmv ±0.3PPmv;>10ppmv ±3%
●Hiki ke hana hou: H2S: <10ppmv ± 0.2ppmv;>10ppmv ±2%
SO2: <10ppmv ±0.2PPmv;>10ppmv ±2%
●Hana hou a hoʻopiha i ka hana: ke keʻena hana hou 2L,manawa hana hou ≤ 5min
Me ka hana hoʻomaloʻo kinoea
●Nui: 395 * 295 * 315mm
●Kaumaha: ma kahi o 5kg.
Mea ho'āʻo nui | 1 apana |
Mea hoʻopili | 1 hoʻonoho |
ʻO ka paipu Teflon (e hoʻokomo i ka valve hoʻoponopono kahe a me ka hoʻohui wikiwiki) | 1 hoʻonoho |
Paipu huelo | 1 hoʻonoho |
ʻāpana ʻāpana | 1 hoʻonoho |
Luna hoʻoili | 1 apana |
Mea hoʻohana's alakai | 1 apana |
Hoike Hoao | 1 apana |