Nā kūlana no ke ana ʻana i ka ratio absorption
ʻAʻole hiki ke ana ʻia ka lākiō absorption a me ka polarization index o ka transformer me ka papa volta o 10kv a me ka hiki o ka mea hoʻololi hoʻolaha pūnaewele ma lalo o 4000kvA.
I ka 220kv a i ʻole ka pae o ka volta transformer a ʻoi aku ka nui ma luna o 120MVA, pono e hoʻohana ʻia ka 5000V insulation resistance tester e ana i ka ratio absorption.ʻAʻole pono e emi ka lākiō absorption ma mua o 1.5 i ka lumi mahana.Ke ʻoi aku ka nui o ka waiwai kūʻē insulation ma mua o 10000MΩ ma R60min, ʻaʻole pono ka polarization index.
GD3126A (GD3126B) Hōʻike Kūʻē Kūʻē 5kV/10TΩ (10kV/20TΩ)
Pono e noʻonoʻo ʻia nā pilikia e pili ana i ke ana ʻana i ka helu absorption ratio polarization index
(1) Pono kēlā me kēia ana e koho i ka mea ho'āʻo kū'ē kū'ē insulation level like, ʻaʻohe hopena o nā mea hana like ʻole;
(2) I ka wā o ke ana ʻana, pono e koho ʻia ka laina hoʻopuka uila kiʻekiʻe e like me kahi laina pale uila kiʻekiʻe kūikawā, a ʻaʻole hiki ke hoʻololi ʻia ka laina hoʻopuka L a me N, ʻaʻole pono e hōʻeha ʻia ka laina hoʻāʻo a hiki ke hoʻokuʻu ʻia i ka hiki;
(3) No ka pale ʻana i ke koena o ka uku i ka hopena o ka hoʻāʻo, pono e hoʻokuʻu ʻia ka mea i hoʻāʻo ʻia ma mua o ka hoʻāʻo;
(4) Ma mua o ka hoʻāʻo ʻana, e wehe i ka uea hoʻāʻo, holoi i ka hui hoʻāʻo maʻemaʻe a e hōʻoia i ka hilinaʻi o ka ʻāina;
(5) No ka pale ʻana i ka mana o ka leakage ili o kēia manawa e like me ka hiki i ka ea humidity kahi hoʻāʻo liʻiliʻi, inā pono e hoʻopili i ke apo pale;
ʻO nā pilikia ma luna aʻe e pono ke nānā ʻia i ka wā e ana i ka helu absorption ratio polarization index.Pono e hoʻolohe i ke koho ʻana o ka volta no nā mea hana mana.Pono ia e like me nā kiko'ī ho'āʻo.