GD3127 Series High Voltage Insulation Resistance Tester
Hoʻohana nui ʻia ʻo GD3127 Series Insulation Resistance Tester i ka mālama ʻana i nā lako uila i loko o ka substation transformer, ka mana mana, a me nā mea ʻē aʻe. RAMP), kānana (FR, 10s, 20s, 30s, 40s 4 mau koho), voltage(V), current(nA) o nā ʻano mea uila kiʻekiʻe a pau, me ka switchgear, transformers, reactors, capacitors, motors, generators and cables, etc.
ʻO GD3127 Series ka mea hana hoʻāʻo maikaʻi loa no ka ʻike mua ʻana a me ka ʻike ʻana i nā hoʻolālā mālama pale a wānana paha no nā hemahema o nā lako.He mea koʻikoʻi nui ia e hōʻoia i ka maikaʻi o ka huahana a me ka palekana o nā kānaka a me nā lako hana.ʻO ka hana insulation o nā huahana uila kekahi o nā hōʻailona koʻikoʻi e loiloi i ka maikaʻi insulation, i hōʻike ʻia e ka hoʻāʻo ʻana i ka insulation resistance.
●Max.pōkole kēia manawa >5mA.
●ʻO ke kū'ēʻana (IR), helu helu polarization (PI), lākiō absorption (DAR).
●Ramp (RAMP), kānana (FR), voltage (V).
●E nānā 'akomi i ka volta ola o ka mea i ana 'ia, a pāpā 'akomi i ka ho'ā'o inā 'oi aku ka volta ma mua o 36V, e pale pono ana i ka mea kani a me ka mea hana.
●Hana manawa, hoʻopaʻa ʻakomi i ka manawa hoʻāʻo.
●Hoʻokuʻu aunoa i ka volta kiʻekiʻe ma hope o ke ana ʻana, ʻaʻole ʻoi aku ka manawa hoʻokuʻu ma mua o 30 kekona.
●Hoʻopau mana ʻakomi.
●Hōʻike dot matrix pale LCD nui me ka hana paʻa.
●ʻO ke ʻano o ka pūpū papalua, paʻa a paʻa, ka pae pale IP65.
●ʻO ka pahu pahu lithium hiki ke hoʻouka hou ʻia.
●ʻO ka hana mālama, hiki iā ia ke mālama i 1000 mau pūʻulu o ka ʻikepili hōʻike manawa maoli me ka lā hoʻāʻo a me ka manawa a me ka manawa hoʻāʻo.
●Hoʻouka i ka hana, hoʻolako ʻia me ka USB interface, hiki ke hoʻouka i ka ʻikepili i ka kamepiula no ka ʻikepili helu ʻikepili.
Hana | ʻO ke kūpaʻa insulation (IR), polarization index (PI), absorption ratio (DAR), ramp (RAMP), kānana (FR, 10s, 20s, 30s, 40s 4 mau koho), voltage(V), current(nA) |
Lako ikehu | Hiki ke kau houpākahi lithium5.2Ah |
Volta koho | GD3127: 250V, 500V, 1kV, 2.5kV, 5kV GD3127B: 250V, 500V, 1kV, 2.5kV, 5kV, 10kV |
Volke uila apololei | (5%-10%)±10V |
ʻO ke ana ʻana o ke kūpaʻa insulation | GD3127:0.50MΩ~2.00TΩ GD3127B: 0.50MΩ~5.00TΩ |
Kaapuni pokole | >5mA |
Helu helu polarization (PI) | ʻAe |
Lakiō hoʻopio (DAR) | ʻAe |
ʻO ke ʻano hoʻāʻo Ramp(RAMP). | E hoʻāʻo i nā ʻanuʻu o 10% o ka volta preset a hiki i ka volta preset |
Kānana hoʻāʻo ʻano | ʻEhā mau koho o 10S, 20S, 30S, 40S |
ʻO ka hoʻāʻo uila | Laulā: AC/DC 0V-1000V, pololei:±5%rdg±3V |
ʻO ka hoʻāʻo o kēia manawa | Laulā: 0.01nA-7mA, pololei:±5%rdg±0.5nA |
Kele uila | E nānā i ka volta o ka mea i hoʻāʻo ʻia, e nānā i ke kūlana hoʻokuʻu ma hope o ka hoʻāʻo ʻana, a pāpā i ka hoʻāʻo inā ʻoi aku ka nui o ka volta ma mua o 36V, pale i ka mea kani a me ka mea hana. |
Ka manawa hoao | Hoʻopaʻa ʻakomi i ka manawa hoʻāʻo, ka palena manawa: 0s~9999s |
Waihona | Ka mālama ʻana i ka ʻikepili hōʻike me ka lā a me ka manawa, he 1000 mau pūʻulu |
Kūkākūkā | Hoʻouka i ka ʻikepili hoʻāʻo i mālama ʻia i ke kamepiula ma o ka laina kamaʻilio USB. |
Batri | Aia kahi hōʻike kiʻekiʻe o ka pākaukau, e hoʻomanaʻo ana e hoʻopaʻa i ka manawa i ka haʻahaʻa o ka puʻupuʻu pila |
Hoʻopau mana ʻakomi | Ua pio ka mana ma hope o 15 mau minuke |
Papa pale | IP65/IP40 |
ʻO ke kūʻokoʻa | 50MΩ(1000V) (ma waena o ke kaapuni hoʻāʻo a me ka pūpū) |
E kū i ka uila | AC 3kV 50Hz 1min (ma waena o ke kaapuni hoʻāʻo a me ka pūpū) |
Nā kūlana | IEC61010-1, IEC61326-1 |
ʻO ka mahana hana a me ka haʻahaʻa | - 20℃ ~ +50 ℃ < 80%RH |
ʻO ka mahana mālama a me ka haʻahaʻa | - 25℃ ~ +65℃80%RH |
Lako ikehu | 220V AC 50Hz |
Ana (mm) | 280(L)*260(W)*160(H) |
Kaumaha | 4400g (me ka pākaukau) |
mea hōʻike kūʻokoʻa hoʻokaʻawale | 1 hoʻonohonoho |
Uea ho'āʻo uila kiʻekiʻe (ʻulaʻula) | 1 ʻāpana |
Uea hoao(ʻōmaʻomaʻo) | 1 ʻāpana |
Hoaouwea(ʻeleʻele) | 1 ʻāpana |
Mea hoʻopili mana | 1 piece |
mea hoʻohanas alakai | 1 kope |
Hoaoreport | 1 kope |