ʻO GDCO-301 Pūnaehana kiaʻi ʻana ma ka pūnaewele o ke kaʻapuni ʻana i kēia manawa ma luna o ke kaula uwea
ʻO nā uwea ma luna o 35kV he mau uwea kumu hoʻokahi me ka pū metala.Ma muli o ka hili ʻia ʻana o ka pahu metala o ke kaula kumu hoʻokahi me ka laina kahua magnetic i hana ʻia e ka mana AC i ka uea kumu, ua loaʻa i nā welau ʻelua o ke kaula kumu hoʻokahi i ka uila hoʻoulu kiʻekiʻe.No laila, pono e lawe ʻia nā ʻano kumu kūpono no ka mālama ʻana i ka volta i hoʻokomo ʻia i loko o ka pae uila palekana (ʻo ka maʻamau ʻaʻole ʻoi aku ma mua o 50V, akā ʻaʻole ʻoi aku ma mua o 100V me nā ana palekana).ʻO ka mea maʻamau, hoʻopaʻa pololei ʻia ka puʻu metala o ka laina pōkole hoʻokahi-core ma kekahi ʻaoʻao a hoʻopaʻa ʻia ma ke āpau a i ʻole pale pale ma kekahi ʻaoʻao.Hoʻokumu ʻia ka puʻu metala o ka laina lōʻihi hoʻokahi - kumu uwea e ka hoʻohui ʻekolu ʻāpana.ʻAʻole pili i ke ʻano o ke ʻano kumu kumu i hoʻopaʻa ʻia, pono ka insulation sheath maikaʻi.Ke hoʻopōʻino ʻia ka insulation o ke kaula, e hoʻopaʻa ʻia ka sheath sheath ma nā wahi he nui, kahi e hoʻoulu ai i ke kahe holo ʻana, e hoʻonui i ka nalowale o ka sheath, e hoʻopilikia i ka hiki ke lawe i kēia manawa o ke kaula, a me ke kumu e puhi ʻia ai ke kaula. no ka wela loa.I ka manawa like, ʻo ka hōʻoia ʻana i ka pae kiʻekiʻe o ke kaula uila e hoʻopaʻa pono ʻia i ka pūnaewele he mea nui loa, inā ʻaʻole hiki ke hoʻopaʻa ʻia ke kumu kumu no nā kumu like ʻole, e piʻi aʻe ka nui o ke kaula metala i nā kilovolts a hiki i nā ʻumi tausani volts. , He mea maʻalahi ke alakaʻi i ka haki ʻana o ka sheath sheath a me ka hoʻokuʻu mau ʻana, e hoʻonui ai i ka wela o ke kaula i waho a i ʻole ke ahi.
Ke hoʻohana nei ʻo GDCO-301 i ke ʻano o kēia manawa.I ka wā ma lalo o nā kūlana maʻamau (ʻo ia hoʻi, hoʻokahi-helu hoʻopaʻa ʻia), ke kaʻapuni ʻana i ke au ma ka sheath, ʻoi aku ka nui o ke au capacitive, liʻiliʻi loa.I ka manawa e puka mai ai ka honua helu lehulehu ma luna o ka puʻu metala a hana i ka loop loop, e piʻi nui ana ke kahe o ke au a hiki ke piʻi aku ma mua o 90% o ke au nui.ʻO ka nānā ʻana i ka manawa maoli o ka holo ʻana o ka pahu metala a me kāna mau hoʻololi ke ʻike i ka nānā ʻana ma ka laina o ka hewa honua he nui o ka pahu metala kelepona hoʻokahi, i ʻike i ka manawa kūpono a me ka pololei o ka hewa o ka honua, e pale pono i ka hanana ʻana o ka ulia pōpilikia a hōʻoia i ka hana palekana a hilinaʻi.
Hoʻohana ia i ka GSM a i ʻole RS485 ma ke ʻano kamaʻilio.He kūpono ia no ka nānā ʻana i nā hewa ʻāina he nui o nā kaula kumu hoʻokahi ma luna o 35kV.
ʻO GDCO-301 Pūnaehana Mākaʻikaʻi Online o ke Kaʻapuni ʻana i kēia manawa ma luna o ka Cable Sheath e loaʻa ana: ʻāpana nui o ka mea nānā i hoʻohui ʻia a me ka mea hoʻololi o kēia manawa, ka wela a me ka ʻike ʻaihue.Hoʻokomo ʻia ka mea hoʻololi o kēia manawa ma ka laina kumu o ke kaula uwea a hoʻololi ʻia i hōʻailona lua ma mua o ka hoʻokomo ʻia ʻana o ka mea nānā.Hoʻohana ʻia ka mea ʻike wela no ka nānā ʻana i ka wela o ke kaula, a hoʻohana ʻia ka mea ʻaihue anti-theft e nānā i ka laina circulation grounding.ʻO ke ʻano o ka ʻōnaehana nānā pūnaewele piha o ka sheath sheath penei:
●ʻO ka nānā ʻana i ka manawa maoli o ke au o ka honua o ʻekolu ʻāpana uwea sheath, ka huina o ka ʻāina a me ka hana ʻana o kēlā me kēia uea kumu nui;
●ʻO ka nānā ʻana i ka manawa maoli o ka mahana uwea ʻekolu-phase;
●ʻO ka nānā ʻana i ka wā maoli anti - ʻaihue i ka hoʻopaʻa ʻia ʻana o ke kaula;
●Hiki ke hoʻonohonoho ʻia ke kaʻina manawa;
●Hiki ke hoʻonohonoho ʻia nā ʻāpana alaala a inā paha e ʻae ʻia nā ʻāpana kiaʻi kūpono e hana i ka alarm;
●E hoʻonoho i ka waiwai kiʻekiʻe, ka liʻiliʻi a me ka waiwai maʻamau i ka manawa i hoʻonohonoho ʻia;
●ʻO ka nānā ʻana i ka manawa maoli o ka lakio o ka nui a me ka liʻiliʻi o ka waiwai o ka pae hoʻokahi o ka honua i loko o ka manawa helu, a me ka hana ʻana i ka alarm;
●ʻO ka nānā ʻana i ka manawa maoli o ka ratio o ka honua i kēia manawa e hoʻouka i loko o ka manawa helu helu, a me ka hana ʻana i ka alarm;
●ʻO ka nānā ʻana i ka manawa maoli o ka loli hoʻololi o ka pae hoʻokahi o ka honua i loko o ka manawa helu helu, a me ka hana ʻana i ka alarm;
●Hiki ke hoʻouna ʻia ka ʻikepili ana i kēlā me kēia manawa.
●Hiki ke kuhikuhi i hoʻokahi a ʻoi aʻe paha nā ʻāpana kiaʻi i ka alarm, e hoʻouna i ka ʻike alarm i ke kelepona paʻa i koho ʻia;
●Ana manawa maoli o ka volta komo;
●Loaʻa i nā ʻikepili nānā a pau nā lepili manawa e hōʻoia i ke ʻano o ka ʻikepili;
●Hiki ke hoʻonohonoho ʻia nā mea nānā a pau e like me nā koi o ka mea hoʻohana;
●Nā kikowaena hoʻoili ʻikepili he nui: RS485 interface, GPRS, GSM SMS, hiki ke hoʻohana i hoʻokahi a ʻoi aku paha nā ʻano hoʻoili ʻikepili i ka manawa like;
●Kākoʻo i ka mālama mamao a me ka hoʻonui;
●ʻO ka hoʻolālā hoʻohana haʻahaʻa haʻahaʻa, kākoʻo i nā ʻano o ka mana: CT induction power, AC-DC mana a me ka mana pākaukau;
●Me nā ʻāpana ʻenehana, me ka hilinaʻi maikaʻi a me ke kūpaʻa;
●Hoʻopili piha ʻia ka modular, maʻalahi e hoʻokomo, lawe ʻia nā ana laka ma nā ʻāpana āpau, maikaʻi ka anti-vibration hana, a maʻalahi ke hoʻololi a wehe;
●Kākoʻo i ka pae palekana IP68.
'ikamu | Nā ʻāpana | |
ʻO kēia manawa
| Ke hana nei i kēia manawa | 1 kaha, 0.5~1000A (Hiki ke hoʻopilikino ʻia) |
Ke au o ka lepo | 4 kaha, 0.5~200A (Hiki ke hoʻopilikino ʻia) | |
Ka pololei ana ana | ±(1%+0.2A) | |
Ka wā ana | 5~200s | |
Mahana | Kaulana | -20 ℃~+180 ℃ |
Ka pololei | ±1 ℃ | |
Ka wā ana | 10~200s |
awa RS485
●Baud rate: 2400bps, 9600bps a me 19200bps hiki ke hoʻonohonoho.
●Ka lōʻihi o ka ʻikepili: 8 bit:
●Bit hoʻomaka: 1 bit;
●Hoʻomaha iki: 1 bit;
●Hoʻopili: ʻaʻohe calibration;
awa GSM/GPRS
●Ka pinepine hana: Quad-band, 850 MHz/900 MHz/1800 MHz/1900 MHz;
●Nā leka pōkole GSM Pākē/English;
●GPRS papa 10, Max.ka māmā hoʻoiho 85.6 kbit/s, Max.hoʻouka i ka wikiwiki 42.8 kbit/s, kākoʻo i ka protocol TCP/IP, FTP a me HTTP.
Lako ikehu
lako mana AC
●Ka uila: 85 ~ 264VAC;
●Ka pinepine: 47 ~ 63Hz;
●Mana: ≤8W
Batri
●Ka uila: 6VDC
●Kaha: hoʻoholo ʻia e ka manawa hana mau o ka pākaukau
●Paʻa pākaukau
Electrostatic discharge immunity | Papa 4:GB/T 17626.2 |
Radio-frequency electro-magnetic field radiation immunity | Papa 3:GB/T 17626.3 |
ʻO ka pale ʻana o ka uila wikiwiki transient/burst | Papa 4:GB/T 17626.4 |
Hoʻonui i ka pale ʻana | Papa 4:GB/T 17626.5 |
Radio-frequency field inductive conduction immunity | Papa 3:GB/T 17626.6 |
ʻO ka mana alapine magnetic field immunity | Papa 5:GB/T 17626.8 |
Pulse magnetic field immunity | Papa 5:GB/T 17626.9 |
Damping oscillation magnetic field immunity | Papa 5:GB/T 17626.10 |
Kuhikuhi maʻamau:
Q/GDW 11223-2014: Hōʻike kikoʻī no ka ʻike mokuʻāina no nā laina kelepona uila kiʻekiʻe.
4.1 Hiki ke hoʻokaʻawale ʻia ka ʻike kelepona i ʻelua mau ʻāpana: ʻike pūnaewele a me ka ʻike pūnaewele.ʻO ka mea mua e pili ana i ka ʻike infrared, ka ʻike ʻana o ka honua i kēia manawa o ka sheath sheath, ka ʻike ʻana i ka wehe ʻana, ʻoiai ka ʻike pūnaewele i loaʻa ka ʻike hoʻokuʻu ʻana ma lalo o ka hoʻāʻo ʻana i ka hoʻāʻo ʻana i ka hoʻāʻo resonant, oscillation cable partial discharge detection.
4.2 Loaʻa i nā ʻano ʻike ʻike kelepona ka hoʻāʻo maʻamau ma kahi ʻano nui, hoʻāʻo hou i nā hōʻailona i manaʻo ʻia, hoʻāʻo ʻia i nā mea hana hewa.Ma kēia ala, hiki ke hōʻoia i ka hana maʻamau o ke kaula.
4.3 Pono nā limahana ʻimi e hele i ka hoʻomaʻamaʻa ʻenehana o ka ʻike kelepona a paʻa i kekahi mau palapala hōʻoia.
4.4 Ke koi kumu o ka terminal infrared imager a me ka honua i kēia manawa e nānā i ka Appendix A. Ke koi kumu o ka hoʻokuʻu hapa haʻahaʻa kiʻekiʻe, ka ʻike hoʻokuʻu hapa kiʻekiʻe kiʻekiʻe a me ka mea ʻike hoʻokuʻu ʻāpana ultrasonic e nānā iā Q/GDW11224-2014.
4.5 E pili ana ka laulā o ka noi i ka Papa 1.
ʻano hana | Ka helu uila o ke kaula | Lae ʻike kī | hemahema | Online/pahemo | ʻŌlelo |
Kiʻi infrared wela | 35kV a ma luna | Terminal, mea hoʻohui | Hoʻopili maikaʻi ʻole, pulu ʻia, kīnā ʻole | Online | Koi ʻia |
Ke au o ka lepo metala | 110kV a ma luna | Pūnaehana kahua | ʻO ke kīnā ʻokoʻa | Online | Koi ʻia |
Hoʻokuʻu hapa hapa alapine kiʻekiʻe | 110kV a ma luna | Terminal, mea hoʻohui | ʻO ke kīnā ʻokoʻa | Online | Koi ʻia |
ʻO ka hoʻokuʻu hapa ʻana i ke alapine ultra kiʻekiʻe | 110kV a ma luna | Terminal, mea hoʻohui | ʻO ke kīnā ʻokoʻa | Online | Koho |
Ka hawewe kani kani | 110kV a ma luna | Terminal, mea hoʻohui | ʻO ke kīnā ʻokoʻa | Online | Koho |
ʻO ka hoʻokuʻu hapa ma lalo o ka ho'āʻo resonant moʻo pinepine | 110kV a ma luna | Terminal, mea hoʻohui | ʻO ke kīnā ʻokoʻa | Pahemo | Koi ʻia |
OWTS oscillation uwea wehe hapa | 35kV | Terminal, mea hoʻohui | ʻO ke kīnā ʻokoʻa | Pahemo | Koi ʻia |
Papa 1
Māka uila | Kau | ʻŌlelo |
110(66)kV | 1. I loko o 1 mahina ma hope o ka hana a i ʻole ka hoʻoponopono nui 2. Hoʻokahi manawa no nā mahina 3 ʻē aʻe 3. Inā pono | 1. Pono e hoʻopōkole ʻia ka manawa ʻike inā loaʻa ka ukana kaumaha ma nā laina uwea a i ʻole i ka wā o ke kau wela. 2. Pono e ʻike pinepine ʻia ma muli o ke ʻano o ka hana ʻino, nā mea hana kahiko, a me nā mea hemahema. 3. Pono e hana ʻia nā hoʻololi kūpono ma muli o nā kūlana o nā mea hana a me nā wahi hana. 4. Hiki ke hoʻololi i ka ʻōnaehana nānā pūnaewele o ke au o ka honua ma luna o ke kaula uwea. |
220kV | 1. I loko o 1 mahina ma hope o ka hana a i ʻole ka hoʻoponopono nui 2. Hoʻokahi manawa no nā mahina 3 ʻē aʻe 3. Inā pono | |
500kV | 1. I loko o 1 mahina ma hope o ka hana a i ʻole ka hoʻoponopono nui 2. Hoʻokahi manawa no nā mahina 3 ʻē aʻe 3. Inā pono |
Papa 4
5.2.3 Nā pae hoʻohālikelike
Pono e hoʻohui i ka ukana o ke kaula a me ke ʻano ʻokoʻa o kēia manawa o ka ʻili kaula me ka ʻikepili ana o ka sheath cable.
E pili ana nā pae hoʻoholo diagnostic i ka Papa 5.
Hoao | Ka hopena | ʻŌlelo aʻo |
Inā hoʻokō ʻia nā koi a pau ma lalo nei: 1. Waiwai loa o ke au o ka honua<50A; 2. Ka lakio ma waena o ke au o ka honua a me ka ukana<20%; 3. Max.waiwai/ Min.ka waiwai o ke au o ka honua<3 | Maʻamau | Hana e like me ka mea maʻamau |
Inā hoʻokō ʻia kekahi koi ma lalo nei: 1. 50A≤ke kumu waiwai o ka honua i kēia manawa ≤100A; 2. 20% ≤ka lākiō ma waena o ka honua a me ka ukana ≤50%; 3. 3≤Max.waiwai/Min.ka waiwai o ka manawa hoʻokahi o ka honua ≤5; | E akahele | E hoʻoikaika i ka nānā ʻana a e hoʻopōkole i ka manawa ʻike |
Inā hoʻokō ʻia kekahi koi ma lalo nei: 1. Waiwai loa o ke au o ka honua>100A; 2. Ka lakio o ke au o ka honua a me ka ukana>50%; 3. Max.waiwai/Min.ka waiwai o ke au o ka honua>5 | hemahema | Hoʻopau a nānā. |
Papa 5